The CI854/CI854A board is in the process of being restarted or configured. Allow time for this to finalize.
If the condition persists, and all other units on the CEX-bus have non-illuminated LEDs:
• Check that a valid HW configuration including the CI854 is downloaded to the controller.
• Check the CEX-bus fuse inside the PM8xx processor unit.
• Initiate a reset signal (INIT) from the PM8xx processor unit.
• Replace the CI854/CI854A unit.
ABB INNTP01
INNTP01 | ABB | Computer Transfer Module
The AC 800M Controller can be powered from an external +24 V DC source. This source is often common for many different types of plant equipment, resulting in long power cables to the AC 800M Controller.